Type of system |
High |
Medium |
Low |
A) Compressor discharge temperature |
120> 210 |
120> 210 |
130> 225 |
B) Condenser liquid line temperature |
less then 135 |
less then 130 |
less then 120 |
C) Evaporator suction temperature |
+31 > +86 |
0 > +40 |
minus 30 > +20 |
D) Compressor suction temperature minus "C" |
0 > 5 deg rise |
3 > 10 deg rise |
5 > 15 deg rise |
E) Outdoor temperature |
50 >+110 |
? > +110 |
? > +110 |
F) Box (Indoor) temp. |
65 > 95 |
20 > 55 |
-40 >+10 |
G) Evaporator air temperature split |
15 > 22 |
8 > 12 |
5 > 10 |
H) Condenser air temperature split |
15 > 30 |
10 > 30 |
5 > 30 |
I) Evaporating Temp. (pressure converted to temp) |
+28 > +50 |
+7 > +35 |
-30 >+10 |
J) Condensing Temp. (pressure converted to temp) |
** 20 to 30 over "E" |
15 to 30 over "E" |
15 to 30 over "E" |
CALCULATED VALUES |
|
|
|
Evaporator superheat "C" minus "I" |
6 > 42* (10 txv) |
3 > 30* (5 txv) |
3 > 40* (3txv) |
Condenser subcooling "J" minus "B" |
0 > 20* 5>25 txv |
0 > 20* 5>20 TXV |
0 > 20* 5>15 TXV |
Evaporator Delta T "F" minus "I" |
30 > 45 |
10 > 25 |
10 > 20 |
Condenser Delta T "E" minus "J" *** |
20 > 35 |
15 > 30 |
15 > 30 |